Cooling System Data
DFEK
50 Degree C Ambient Radiator Cooling System
Max Cooling @ Air Flow Static Restriction, Unhoused
(inches water/mm water)
Housed in Free Air, No Air Discharge
Restriction
0.0/0.0 0.25/6.4 0.5/12.7 0.75/19.1 1.0/25.4 F183 F184 F200 F201 F202
Duty
Rating
(kW)
Maximum Allowable Ambient Temperature, Degree C
Standby 500 55 55 55 55 55 N/A N/A 54 54 53
60Hz
Prime 455 55 55 55 55 55 N/A N/A N/A N/A N/A
Standby 440 55 55 55 55 54 N/A N/A N/A N/A N/A
50Hz
Prime 400 55 55 55 55 53 N/A N/A N/A N/A N/A
Notes:
1. Data shown are anticipated cooling performance for typical generator set.
2. Cooling data is based on 1000 ft (305 m) site test location.
3. Generator set power output may need to be reduced at high ambient conditions. Consult generator set data sheet for derate schedules.
4. Cooling performance may be reduced due to several factors including but not limited to: Incorrect installation, improper operation, fouling of the
cooling system, and other site installation variables.
Cummins Power Generation
Specification May Change Without Notice
Bulletin mcp-105e
Page view 37