PROTOTYPE TEST SUPPORT (PTS)
60 HZ TEST SUMMARY
GENERATOR SET MODELS REPRESENTATIVE PROTOTYPE
350DFEG
400DFEH
450DFEJ
500DFEK
The following summarizes prototype testing conducted on the designated representative prototype of the specified models.
This testing is conducted to verify the complete generator set electrical and mechanical design integrity. Prototype testing is
conducted only on generator sets not sold as new equipment.
Maximum Surge Power:
kW
516
Maximum Motor Starting:
kVA
2429
The generator set was tested to simulate motor starting by
applying the specified kVA load at low lagging power factor
(0.4 or lower). With this load applied, the generator set
recovered to a minimum of 90% rated voltage.
Torsional Analysis and Testing:
The generator set was tested to verify that the design is not
subjected to harmful torsional stresses in excess of 5000 psi.
A spectrum analysis of the transducer output was conducted
over the speed range of 1200 to 2000 RPM.
Cooling System:
ºC Ambient50
in. H2O restriction0.5
The cooling system was tested to determine ambient
temperature and static restriction capabilities. The test was
performed at full rated load in elevated ambient temperature
under static restriction conditions.
Durability:
Steady State Performance:
The generator set was tested to verify steady state operating
performance was within the specified maximum limits.
Voltage Regulation:
Random Voltage Variation:
Frequency Regulation:
Random Frequency Variation:
Transient Performance:
The generator set was tested with the standard alternator to
verify single step loading capability as required by NFPA 110
and verify acceptable voltage and frequency response on
load addition or rejection. The following results were
recorded:
Full Load Acceptance:
Voltage Dip:
Recovery Time:
Frequency Dip:
Recovery Time:
Full Load Rejection:
Voltage Rise:
Recovery Time:
Frequency Rise:
Recovery Time:
Harmonic Analysis:
(per MIL-STD-705B, Method 601.4)
Harmonic No Load Full LOad No Load Full Load
Line to Line Line to Neutral
3
5
7
9
11
13
15
Electrical and Mechanical Strength:
The generator set was tested to several single phase and
three phase faults to verify that the generator can safely
withstand the forces associated with short circuit conditions.
The generator set was capable of producing full rated output
at the conclusion of the testing.
Model:
Engine:
Alternator:
QSX15-G9
HC5F
500DFEK
0.044
2.5
1.1
0.066
0.72
0.3
0.012
0.026
2.1
0.58
0.014
0.77
0.235
0.18
0.104
0.38
0.42
0.033
0.74
0.25
0.02
0.1
0.36
0.42
0
0.74
0.2
0
%32.1
Second3.4
%10.8
Second4
%16.3
Second0.9
%4
0.6 Second
%0.5
%0.3
Isochronous
%
0.25
±
±
±
The generator set was subjected to a minimum 500 hour
endurance test operating at varialbe load up to the standby
rating based upon MIL-STD-705 to verify structural soundness
and durability of the design.
The generator set was evaluated to determine the stated
maximum surge power.
Cummins Power Generation
Specification May Change Without Notice PTS-145B